Reaction to Fire of Construction Materials
In systems where the use of micro-perforated fabric ducts is planned, it is important to pay attention to the Reaction to Fire Class required for the specific application.
Field of application in high-induction micro-perforated ducts.
Since European regulations have introduced a different classification compared to Italian standards, in this short article we would like to explore the meaning of the acronyms and the resulting importance of choosing the right materials from which micro-perforated ducts are manufactured. First of all, let us clarify the difference between fire resistance and reaction to fire:
- The former refers to the ability of a product/construction element to maintain integrity and insulation for a specified period of time.
- REACTION TO FIRE of a material, on the other hand, is the contribution it makes to fueling a fire when exposed to it.
For fire prevention purposes, European standards have defined a classification criterion for construction products based on EUROCLASSES, introduced to create a common platform that allows fire properties to be compared. The main properties that define the class to which a given product belongs – in our case, the micro-perforated duct – are:
-
combustibility,
-
flammability,
-
calorific value,
-
smoke production and flaming droplets
All these characteristics are evaluated according to specific laboratory tests defined by the EN 13501 standard. It introduces a main classification and an additional classification. The main classification is identified by a capital letter:
- A1 identifies NON-COMBUSTIBLE products.
All other classes group combustible products according to their increasing contribution to a fire:
-
A2, B= non-flammable combustibles
-
C, D= not easily flammable combustibles
-
E, F= easily flammable combustibles.

Laboratory workstation for fire resistance testing
The classification is completed by the parameter s (smoke), relating to smoke emissions, where the values s1, s2, s3 indicate a progressively increasing optical smoke density, and by the parameter d (dropping), relating to flaming droplets/particles, where the values d0, d1, d2 indicate a progressively increasing hazard of dripping.
Between old and new regulations.
Many fire prevention decrees still in force refer to the reaction to fire classes of the old Italian regulations. To resolve this issue, the Ministry of the Interior issued conversion tables with the Ministerial Decree of March 15, 2005. The table below is an example relating to materials used on ceilings:
|
Italian Class |
European Class |
|
Class 0 |
A1 |
|
Class 1 |
A2-s1, d0 / A2-s2, d0 / A2-s3, d0 / A2-s1, d1 / A2-s2, d1 / A2-s3, d1 / B-s1, d0 / B-s2, d0 / B-s3, d0 |
|
Class 2 |
B-s1, d1 / B-s2, d1 / B-s3, d1 / C-s1, d0 / C-s2, d0 / C-s3, d0 |
|
Class 3 |
C-s1, d1 / C-s2, d1 / C-s3, d1 / D-s1, d0 / D-s2, d0 |
According to this classification, FIBER POWER JET, fabric ducts manufactured by Vector meet the following ratings:
-
Mineral fiber diffusers: Euroclass A1
-
Polyester diffusers: Euroclass B-s1, d0
-

Installation example of Euroclass A1 mineral fiber diffusers
As for GALVANIZED STEEL micro-perforated ducts (Steel Power Jet), the Ministerial Decree of 14/01/1985 automatically assigns Class 0 (A1) to galvanized products or those with an inorganic-based surface finish. Polyester-based pre-painted micro-perforated diffusers also normally fall under the A1 classification, the declaration of which is issued upon request by the steel mill of origin. .
For any further information, please contact the VECTOR technical office, which can provide qualified consultancy and analysis for the design and development of systems with micro-perforated ducts.