Balancing Air Distribution Networks with Micro-Perforated Ducts
Discover the advantage of proper system balancing without the use of volume control dampers
A distinctive feature of high-induction micro-perforated diffusers is that they are specifically sized for each individual project.
How air distribution network balancing is achieved with micro-perforated ducts.
The calibration of the perforation pattern—resulting from the calculations of Vector’s technical office using dedicated sizing software—allows the system to be balanced by selecting the exact operating point on the characteristic curve with absolute precision. This yields the major advantage of achieving proper air distribution without needing volume control dampers upstream of the diffusing sections.
Traditional system with dampers and grilles |
System with micro-perforated diffusers |
The solution to adopt in “hybrid” systems
In air distribution networks with “hybrid” distribution systems—that is, when more traditional terminals (e.g., grilles) are used for certain zones served by the same air conditioning unit—these terminals must be positioned downstream of the micro-perforated diffusers and equipped with balancing dampers in order to maintain the design balance.
This sound design rule makes it possible to maintain the required static pressure at the inlet of the perforated ducts and achieve an optimal induction effect


Traditional system with dampers and grilles