DESIGN GUIDE FOR PERMEABLE DUCTS
STEP-BY-STEP SIZING PROCEDURE PERMEABLE FABRIC DIFFUSERS
Given the dimensions of the room and the hourly air volumes to be supplied, the number of diffusers is determined. As a design criterion, consider a treated area, for each side of the individual diffuser, equal to 0.5 to 1 times the installation height of the duct.
Once the flow rate of each diffuser has been established, proceed with duct sizing by selecting its diameter using the charts in FIG. 1 and FIG. 2
FIG.1

FIG.2

By locating the flow rate on the vertical axis, you can determine the permissible diameters, the corresponding internal air velocities, and the dynamic pressure (Pd) (detailed more precisely in chart FIG. 3) required at the inlet to ensure proper inflation of the diffuser.
FIG.3

As shown in the table, it is advisable to maintain internal velocities below 10 m/s to prevent excessive turbulence. Where possible, it is recommended to select diameters with relative velocities of approximately 6–7 m/s, as these correspond to lower Pd e di Pmin values.
Using the obtained diameter, proceed to calculate the flow rate per square meter to be diffused (F), a value obtained through the following formula:
F = Q / Sl
where Q is the flow rate supplying the duct and $Sl$ is the diffusing lateral surface area of the duct.
Using chart FIG. 6, you can then determine the permissible permeability values and the corresponding Static Pressure (Pst) required for air distribution.

With these values, verify that the Useful Total Pressure (Pt) is greater than the Pmin obtained when selecting the diameter, knowing that:
Pt = Pst + Pd
If this condition is not met, it will be necessary to select a fabric type corresponding to a higher Pst until the aforementioned requirement is satisfied.
NUMERICAL EXAMPLE:
Sizing of a circular porous duct for cooling a room with the following characteristics:
-
Length: 9 m;
-
Width: 5 m;
-
Height: 3 m;
To achieve an air change rate of 30 volumes/h, a required flow rate (Q) will be:
Q = 30 h-1 ⋅ 135 m3 = 4050 m3/h
From table FIG. 1, we obtain:
D=400 mm Pd=50 Pa Pmin = 120 Pa
Select a Duct length L = 8m, leaving a 1 m clearance relative to the room length for connection to the air handling unit or its positioning.
For the lateral surface area (Sl), we get:
Sl = πD ⋅ L = 10 m2
Consequently, the permeability (F) is:
F = Q / Sl = 405 m3/h / m2
From table FIG. 4, select for example a V600 fabric with:
Pst = 60 Pa
And therefore, for the final verification:
Pt > Pmin
Pt = Pst + Pd = 108 Pa < 120 Pa
The selected fabric is therefore unsuitable; proceed to select one with a higher Pst, for example a V450:
Pst = 90 Pa
Pt > Pmin
Pt = Pst + Pd = 140 Pa > 110 Pa
The selected fabric is therefore suitable, and the duct will have the following characteristics:
-
Length: 8 m;
-
Diameter: 400 mm;
-
Fabric: V450.
And it will be supplied by a unit set at the operating point with:
-
Flow rate: 4,050 m³/h;
-
Pressure: 140 Pa.