DESIGN GUIDE FOR PERFORATED DUCTS

WIZARD PROCEDURE FOR SIZING HIGH-INDUCTION MICRO-PERFORATED DUCTS

Given the dimensions of the room and the hourly air volumes to be supplied, the number of diffusers is determined. As a design criterion, consider a treated area, for each side of the individual diffuser, equal to 1.5 to 2 times the installation height of the duct.

It is possible to design diffusing ducts with a wider range of action, but in this case, since more precise evaluations are required, the support of VECTOR technical department is essential.

Once the flow rate of each diffuser has been established, proceed with duct sizing by selecting its diameter using chart FIG. 1 (for semicircular diffusers, see FIG. 2). By locating the flow rate on the vertical axis, you can determine the permissible diameters, the corresponding internal air velocities, and the dynamic pressure (Pd) (detailed more precisely in chart FIG. 3).

FIG.1

FIG. 2

As highlighted in the table, for fabric ducts, it is advisable to maintain internal velocities below 10 m/s to prevent excessive turbulence that could cause noticeable vibration in the fabric walls of the duct, as well as generate an unbalanced flow with unwanted axial components that tend to push the supplied air toward the far end of the room being treated.

For metal ducts, it is recommended not to exceed 7 m/s to avoid the generation of noise caused by air friction against the internal surface of the duct.

As a final step, select the optimal (minimum) pressure required at the duct inlet using chart FIG. 4.

FIG. 3   

FIG. 4

Using the chart in FIG. 5, in the case of metal perforated diffusers, you can also determine the sound power level Lw(A) generated by air discharging through the perforations as a function of the static pressure inside the duct.

For fabric ducts, this component can be considered negligible due to the high sound-absorbing capacity of the fabric.

. 

FIG.5

NUMERICAL EXAMPLE:

Sizing of an air conditioning/treatment system for a room with the following characteristics:
Length: 60 m;
Width: 45 m;
Height: 7.5 m;

To achieve an air change rate of 2 volumes/h, a total flow rate (Q) of:
Qtot = 2 h-1 ⋅ (60 m ⋅ 45 m ⋅ 7.5 m) = 40,500 m³/h

Assuming an installation height (H) of 7 m, a treated area of approximately 14 m per side can be considered. Therefore, two longitudinally positioned ducts, each 58 m long (leaving a 2 m clearance relative to the room length for connection to the air handling unit or its positioning), will be sufficient to treat the entire space.

Assuming you want to treat the space uniformly, dividing the total flow rate by the number of ducts yields a flow rate per individual duct of Q = 20,250 m³/h.

Assuming circular cross-section ducts, table 4.6.2 gives a diameter D = 1,000 mm with an internal velocity slightly above 7 m/s.

Finally, using table 4.6.5, for a duct installed at a height of 7 m, the indicated pressure required at the diffuser inlet is 220 Pa.

Thus, the air distribution system will be structured as follows:
– Number of ducts: 2 pcs
– Length: 58 m
– Diameter: 1000 mm
– Installation height: 7 m
– Flow rate: 20,250 m³/h
– Inlet pressure: 220 Pa

Vector
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.